- 1Scope
This specification covers the general requirements of corrugated high density polyethylene (HDPE) pipe with a smooth interior for use in storm sewer and engineered projects requiring leak-resistant joints.
-
2Material
Pipe shall be manufactured and certified to have met all requirements set out in CAN/CSA, B182.6-02 and/or B182.8-02, Profile Polyethylene Sewer Pipe and Fittings. Resistant to a wide range of soil acidity: pH 1.25 to 14.
-
3Joining Systems
The pipe shall be joined with gasketed bell and spigot. Meets or exceeds 100 kPa (15 psi) per ATM 3212.
-
4Pipe Stiffness
Pipe shall have minimum pipe stiffness of 320 kPa at 5% deflection with tested in accordance with ASTM D2412.
-
5Hydraulics
A Manning's 'n' value of 0.010 shall be used to calculate the flow for all sizes of smooth interior CHALLENGER 3000 Pipe. See CPPA Technical Hydraulic booklet available from Ideal Pipe or the Plastics Pipe Institute.
-
6Structural Design
Structural design shall conform to the industry accepted procedures found in the Corrugated Polyethylene Pipe Association's technical booklets from Ideal Pipe or the Plastics Pipe Institute.
-
7Applicable Standards
CAN/CSA B182.6-02
B182.8-02
ASTM D3350
OPSS 1840
OPSD 806.02
-
8Options
Available as solid, perforated or filtered pipe.
-
9Pipe Dimensions
Standard pipe lengths shall be 4 m (16') or as needed to meet job requirements. Nominal pipe size is based on inside diameter of the pipe.
| Nominal (inches) | ID | OD | Bell OD | Weight (kg/m) |
| 6 | 150mm | 175mm | 185mm | 1.4 |
| 8 | 200mm | 235mm | 245mm | 2.5 |
| 10 | 250mm | 295mm | 310mm | 4.0 |
| 12 | 300mm | 370mm | 390mm | 6.0 |
| 15 | 375mm | 450mm | 475mm | 7.5 |
| 18 | 450mm | 530mm | 560mm | 11.5 |
| 21 | 525mm | 630mm | 670mm | 16.5 |
| 24 | 600mm | 715mm | 760mm | 19.5 |
| 30 | 750mm | 885mm | 925mm | 30.0 |